Schneider Electric | ZENL1121 | Contact Block

Call Us +65 8693 8729
phone 0
phone 0
Product

Industrial Automation

ZENL1121 - Contact Block - NC

  • $9.24

Harmony XALD, XALK, Single contact block, silver alloy, screw clamp terminal, 1 NC

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range of product Harmony XAPS
Harmony XAL
product or component type Contact block
device short name ZENL
product destination For XAPS control station
For XB5 Ø 22 mm control and signalling units
mounting of block Rear mounting
sale per indivisible quantity 5
contacts type and composition      1 NC
assembly style For customer assembly
product weight 0.015 kg
contact operation Slow-break
positive opening With conforming to EN/IEC 60947-5-1 appendix K
operating travel 1.5 mm (NC changing electrical state)
4.3 mm (total travel)
operating force 2 N NC changing electrical state
mechanical durability 10000000 cycles
connections - terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
tightening torque 0.8…1.2 N.m conforming to EN 60947-1
shape of screw head Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
contacts material Silver alloy (Ag/Ni)
maximum resistance across terminals      25 MOhm
short-circuit protection 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current      10 A conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage 600 V (pollution degree 3) conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage      6 kV conforming to EN/IEC 60947-1
[Ie] rated operational current 3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
electrical durability 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
electrical reliability Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 5 mA conforming to EN/IEC 60947-5-4
additional information Mounting on integrated plate in the box
electrical composition code SR1 (quantity <= 3)
SR2 (quantity <= 2)
MR1 (quantity <= 2)