Schneider Electric | XMLR016G1P25 | Pressure Transmitter

Call Us +65 8693 8729
phone 0
phone 0
Product

Industrial Automation

XMLR016G1P25 - Pressure Transmitter - 16 Bar

  • $662.41

Electronic pressure sensors, Pressure sensors XM, XMLR 16 bar, G 1/4, 24 VDC, 4...20 mA, PNP, M12

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range of product OsiSense XM
product or component type Electronic pressure sensors
pressure sensor type Pressure transmitter
pressure switch type of operation Pressure transmitter with 1 switching output
device short name XMLR
pressure rating 1599.58 kPa
16 bar
maximum permissible accidental pressure      6205.28 kPa
62 bar
6.2 MPa
destruction pressure 6205.28 kPa
62 bar
6.2 MPa
controlled fluid Fresh water (0…80 °C)
Air (-20…80 °C)
Hydraulic oil (-20…80 °C)
Refrigeration fluid (-20…80 °C)
fluid connection type G 1/4 (female) conforming to DIN 3852-Y
[Us] rated supply voltage 24 V DC SELV (voltage limits: 17…33 V)
current consumption <= 50 mA
electrical connection Male connector M12, 4 pins
analogue output function 4...20 mA
type of output signal Analogue + discrete
analogue output function 4...20 mA
discrete output type Solid-state PNP, NO/NC programmable
maximum switching current 250 mA
contacts type and composition NO/NC programmable
scale type Fixed differential
maximum voltage drop 2 V
adjustable range of switching point on rising pressure      128.24…1599.58 kPa
1.28…16 bar
0.128…1.6 MPa
adjustable range of switching point on falling pressure      79.98…1551.32 kPa
0.08…1.55 MPa
0.8…15.5 bar
minimum differential travel 48 kPa
48.26 kPa
0.48 bar
materials in contact with fluid Fluorocarbon FKM (Viton)
Ceramic
316L stainless steel
front material Polyester
housing material 316L stainless steel
Polyacrylamide
operating position Any position, but disposals can falsify the measurement in case of upside-down mounting
protection type Short-circuit protection
Overload protection
Overvoltage protection
Reverse polarity
response time on output <= 10 ms for analog output
<= 5 ms for discrete output
switching output time delay 0...50 s in steps of 1 second
display type 4 digits 7 segments
local signalling 1 LED (yellow) for light ON when switch is actuated
display response time type Fast 50 ms
Normal 200 ms
Slow 600 ms
maximum delay first up 300 ms
overall accuracy <= 1 % of the measuring range
linearity error on analogue output <= 0.5 % of the measuring range
hysteresis on analogue output <= 0.2 % of the measuring range
measurement accuracy on switching output <= 0.6 % of the measuring range
repeat accuracy <= 0.2 % of the measuring range
drift of the sensitivity +/- 0.03 % of measuring range/°C
drift of the zero point +/- 0.1 % of measuring range/°C
display accuracy <= 1 % of the measuring range
mechanical durability 10000000 cycles
depth 42 mm
height 93 mm
width 41 mm
net weight 0.19 kg
[Uimp] rated impulse withstand voltage 0.5 kV DC
electromagnetic compatibility Susceptibility to electromagnetic fields: 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances: 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
Surge immunity test: 1 kV conforming to EN/IEC 61000-4-5
Electrical fast transient/burst immunity test: 2 kV conforming to EN/IEC 61000-4-4
Electrostatic discharge immunity test: 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2