Industrial Automation
XALK198 - Control Station - 1NC
-
$43.89
Harmony XALD, XALK, Control station, plastic, yellow, 1 red mushroom head push button Ø40, emergency stop push-pull 1 NC, unmarked
Out Of Stock
This product is out of stock, submit your email and we will update once it restock.
range of product | Harmony XALK |
---|---|
product or component type | Complete control station |
device short name | XALK |
product destination | For XB5 Ø 22 mm control and signalling units |
control station application | Emergency stop function Emergency switching off function |
colour of base of enclosure | Light grey (RAL 7035) |
colour of cover | Yellow (RAL 1021) |
material | Polycarbonate |
operator profile | 1 mushroom head push-button |
operators description | Red unmarked 1 NC |
reset | Push-pull |
control station composition | 1 mushroom head Ø 40 mm push-button, red 1 NC unmarked marking |
contact operation | Slow-break |
cable entry | 1 knock-out for cable entry 0…14 mm 2 knock-outs for Pg 13 cable gland and ISO M20 0…12 mm |
---|---|
product weight | 0.183 kg |
resistance to high pressure washer | 7000000 Pa at 55 °C, distance : 0.1 m |
positive opening | With conforming to EN/IEC 60947-5-1 appendix K |
operating travel | 1.5 mm (NC changing electrical state) 4.3 mm (total travel) |
operating force | 50 N |
mechanical durability | 300000 cycles |
connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1 |
tightening torque | 0.8…1.2 N.m conforming to EN/IEC 60947-1 |
shape of screw head | Cross compatible with Philips no 1 screwdriver Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver |
contacts material | Silver alloy (Ag/Ni) |
short-circuit protection | 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1 |
[Ith] conventional free air thermal current | 10 A conforming to EN/IEC 60947-5-1 |
[Ui] rated insulation voltage | 600 V (pollution degree 3) conforming to EN/IEC 60947-1 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-1 |
[Ie] rated operational current | 3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1 6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1 |
electrical durability | 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
electrical reliability | Λ < 10exp(-6) at 5 V, 1 mA conforming to EN/IEC 60947-5-4 Λ < 10exp(-8) at 17 V, 5 mA conforming to EN/IEC 60947-5-4 |