Modular 1-phase voltage control relay, 5 A, 2 CO, range 1..100 V, 24..240 V AC/DC

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range of product Harmony Control Relays
product or component type Voltage control relay
relay type Multifunction voltage control relay
relay name RM35UA
relay monitored parameters Overvoltage or undervoltage detection
time delay Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold
switching capacity in VA 1250 VA
minimum switching current 10 mA at 5 V DC
maximum switching current 5 A AC/DC
power consumption in VA 0…3.5 VA AC
measurement range 1...100 V voltage
utilisation category AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
contacts type and composition      2 C/O
reset time 1500 ms time delay
maximum switching voltage 250 V AC/DC
[Us] rated supply voltage 24...240 V AC/DC 50/60 Hz +/- 10 %
supply voltage limits 20.4…264 V AC/DC
maximum power consumption in W      0.6 W DC
immunity to microbreaks 10 ms
control circuit frequency 40...70 Hz +/- 10 %
resistance across terminals 110 mOhm at E2-M terminals
22 mOhm at E1-M terminals
220 mOhm at E3-M terminals
output contacts 2 C/O
nominal output current 5 A
maximum measuring cycle 30 ms measurement cycle as the true rms value
hysteresis 5…50 % of threshold setting
delay at power-up 600 ms
measurement accuracy +/- 10 % of the full-scale value
repeat accuracy +/- 0.5 % for input and measurement circuit
+/- 2 % for time delay
measurement error +/- 0.05 %/°C with temperature variation
< 1 % over the whole range with a voltage variation
polarity Non-reversible polarity on DC supply
sensitivity scale 1...10 V E1-M terminals
10...100 V E3-M terminals
5...50 V E2-M terminals
threshold setting 10...100 %
quality labels CE
overvoltage category III conforming to IEC 60664-1
insulation resistance > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
[Ui] rated insulation voltage 250 V conforming to IEC 60664-1
600 V conforming to IEC 60664-1
operating voltage tolerance - 15 % + 10 % Un
operating position Any position without derating
connections - terminals Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
tightening torque 0.6…1 N.m conforming to IEC 60947-1
housing material Self-extinguishing plastic
local signalling LED (green) for power ON
LED (yellow) for relay ON
mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
electrical durability 100000 cycles
mechanical durability 30000000 cycles
operating rate <= 360 operations/hour full load
safety reliability data B10d = 290000
MTTFd = 308.2 years
width 35 mm
net weight 0.08 kg
compatibility code RM3