Schneider Electric | LV847225 | Air Circuit Breaker

Call Us +65 8693 8729
phone 0
phone 0
Product

Power Distribution

LV847225 - MTZ - 1000A - 4P - Drawout

  • $3,273.90

ACB MTZ1 10H1, 1000 A, 4P drawout, without Micrologic

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range Masterpact
product name Masterpact MTZ1
device short name MTZ1 10 H1
product or component type      Circuit breaker
device application Protection
poles description 4P
neutral position Left
network type AC
network frequency 50/60 Hz
breaking capacity code H1
suitability for isolation Yes conforming to IEC 60947-2
selectivity category Category B
control type Push-button
mounting mode Drawout
mounting support Rails
Base plate
[In] rated current 1000 A at 40 °C
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making capacity      88 kA 220/415 V AC at 50/60 Hz
88 kA 440 V AC at 50/60 Hz
88 kA 500/525 V AC at 50/60 Hz
88 kA 660/690 V AC at 50/60 Hz
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT rating 630 A
400 A
800 A
1000 A
performance level 42 kA Icu at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 42 kA at 220/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability 12500 cycles with periodic preventive maintenance conforming to IEC 60947-2
electrical durability 3000 cycles 690 V AC 50/60 Hz conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz conforming to IEC 60947-2
AC-23A: 3000 cycles 690 V AC 50/60 Hz conforming to IEC 60947-3
AC-23A: 6000 cycles 440 V AC 50/60 Hz conforming to IEC 60947-3
AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to IEC 60947-3
connection pitch 70 mm
[Icw] rated short-time withstand current 42 kA 0.5 s conforming to IEC 60947-2
42 kA 1 s conforming to IEC 60947-2
24 kA 3 s conforming to IEC 60947-2
maximum breaking time 25 ms
maximum closing response time 50 ms
height Drawout circuit breaker without chassis: 259.5 mm
Drawout circuit breaker with chassis: 322 mm
width Drawout circuit breaker without chassis: 306.5 mm
Drawout circuit breaker with chassis: 358 mm
depth Drawout circuit breaker without chassis: 207.5 mm
Drawout circuit breaker with chassis: 266 mm