Schneider Electric | LR9G225 | Thermal Overload Relay

Call Us +65 8693 8729
phone 0
phone 0
Product

Industrial Automation

LR9G225 - Electronic T.O.R - 57-225A

  • $674.10

Electronic thermal overload relay, TeSys Giga, 57…225 A, class 5E…30E, push-in control connection

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range TeSys
product name TeSys LRG
product or component type Electronic thermal overload relay
device short name LR9G
relay application Motor protection
network type AC
thermal overload class Class 5E...30E conforming to IEC 60947-4-1
thermal protection adjustment range      57…225 A
network frequency 30...60 Hz
100 Hz
overvoltage category III
tripping threshold 1.125 +/- 0.07 In conforming to IEC 60947-4-1
protection type Ground fault protection - tripping time adjustment: 0…1 s - for alarm circuit conforming to IEC 60947-4-1
Ground fault protection - tripping time adjustment: 0…1 s - for alarm circuit conforming to UL 60947-4-1
Phase loss - tripping time adjustment: 0…4 s - for alarm circuit
Phase imbalance - tripping time adjustment: 0…5 s - for alarm circuit conforming to IEC 60947-4-1
Phase imbalance - tripping time adjustment: 0…5 s - for alarm circuit conforming to UL 60947-4-1
local signalling LED
Trip indicator
contacts type and composition 1 NO + 1 NC
[Ith] conventional free air thermal current      5 A
[Uc] control circuit voltage 24...500 V AC 50/60 Hz
24...250 V DC
[Ue] rated operational voltage 1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
reset Automatic reset
Manual
mechanical durability 7000 cycles
surge withstand 4 kV
electromagnetic compatibility EMC immunity conforming to IEC 60947-4-1
Emission tests criteria A conforming to IEC 60947-4-1
Immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3
Voltage dips and interruptions immunity test conforming to SEMI F47
connections - terminals Power circuit: bar - busbar cross section: 25 x 6 mm
Power circuit: lugs-ring terminals 1 185 mm²
Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end
Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: push-in 2 0.5…1.0 mm² with cable end
tightening torque 18 N.m
mounting support Direct on contactor
Plate
standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
JIS C8201-4-1
JIS C8201-5-1
product certifications CB Scheme
CCC
cULus
UKCA
ATEX
EU-RO-MR by DNV-GL
EAC