LC1G400KUEN - Contactor - 400A - 100-250VAC/DC

  • $2,996.00

High power contactor, TeSys Giga, 3 pole (3NO), AC-3 <=440V 400A, advanced version, 100…250V wide band AC/DC coil

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range TeSys
range of product TeSys Giga
product or component type Contactor
device short name LC1G
contactor application Power switching
Motor control
utilisation category AC-1
AC-3
AC-3e
AC-4
AC-5a
AC-5b
AC-6a
AC-6b
AC-8b
AC-8a
DC-1
DC-3
DC-5
poles description 3P
[Ue] rated operational voltage      <= 1000 V AC 50/60 Hz
<= 300 V DC
[Ie] rated operational current      550 A (at <40 °C) at 440 V AC-1
400 A (at <40 °C) at 440 V AC-3
[Uc] control circuit voltage 200...500 V AC/DC 50/60 Hz
colour Dark grey
[Uimp] rated impulse withstand voltage 8 kV
Overvoltage category III
[Ith] conventional free air thermal current 550 A (at 40 °C)
Rated breaking capacity 3480 A at 440 V
[Icw] rated short-time withstand current 3.6 kA - 10 s
2.4 kA - 30 s
1.7 kA - 1 min
1.2 kA - 3 min
1.0 kA - 10 min
Associated fuse rating 500 A aM at <= 440 V for motor
315 A aM at <= 690 V for motor
630 A gG at <= 690 V
Average impedance 0.0001 Ohm
[Ui] rated insulation voltage 1000 V
Power dissipation per pole 30 W AC-1 - Ith 550 A
16 W AC-3 - Ith 400 A
Compatibility code LC1G
Pole contact composition 3 NO
Auxiliary contact composition 1 NO + 1 NC
Network frequency 50/60 Hz
16.67...400 Hz (with derating)
Motor power kW 110 kW at 230 V AC 50/60 Hz (AC-3e)
200 kW at 400 V AC 50/60 Hz (AC-3e)
200 kW at 415 V AC 50/60 Hz (AC-3e)
250 kW at 440 V AC 50/60 Hz (AC-3e)
250 kW at 500 V AC 50/60 Hz (AC-3e)
315 kW at 690 V AC 50/60 Hz (AC-3e)
220 kW at 1000 V AC 50/60 Hz (AC-3e)
110 kW at 230 V AC 50/60 Hz (AC-3)
200 kW at 400 V AC 50/60 Hz (AC-3)
200 kW at 415 V AC 50/60 Hz (AC-3)
250 kW at 440 V AC 50/60 Hz (AC-3)
250 kW at 500 V AC 50/60 Hz (AC-3)
315 kW at 690 V AC 50/60 Hz (AC-3)
220 kW at 1000 V AC 50/60 Hz (AC-3)
110 kW at 230 V AC 50/60 Hz (AC-4)
200 kW at 400 V AC 50/60 Hz (AC-4)
200 kW at 415 V AC 50/60 Hz (AC-4)
220 kW at 440 V AC 50/60 Hz (AC-4)
250 kW at 500 V AC 50/60 Hz (AC-4)
315 kW at 690 V AC 50/60 Hz (AC-4)
220 kW at 1000 V AC 50/60 Hz (AC-4)
Motor power hp 125 hp at 200/208 V 60 Hz
150 hp at 230/240 V 60 Hz
300 hp at 460/480 V 60 Hz
400 hp at 575/600 V 60 Hz
Irms rated making capacity 5090 A at 440 V
Control circuit voltage limits Operational: 0.8...1.1 Uc AC/DC (at 60 °C)
Drop-out: 0.1...0.45 Uc AC/DC (at 60 °C)
Coil technology Built-in bidirectional peak limiting
Mechanical durability 5 Mcycles
8 Mcycles with sub-assembly substitution
inrush power in VA (50/60 Hz, AC) 750 VA
inrush power in W (DC) 660 W
hold-in power consumption in VA (50/60 Hz, AC)      15.5 VA
hold-in power consumption in W (DC) 9.3 W
Operating time 40...70 ms closing
15...50 ms opening
Maximum operating rate 300 cyc/h AC-1
500 cyc/h AC-3
500 cyc/h AC-3e
150 cyc/h AC-4
Connections - terminals Power circuit: bar 2 - busbar cross section: 32 x 10 mm
Power circuit: lugs-ring terminals 1 185 mm²
Power circuit: bolted connection
Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end
Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: push-in 2 0.5…1.0 mm² with cable end
Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable end
Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
Connection pitch 45 mm
mounting support Plate
Standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
JIS C8201-4-1
JIS C8201-5-1
Product certifications CB Scheme
CCC
cULus
EAC
CE
UKCA
EU-RO-MR by DNV-GL
Tightening torque 35 N.m
Height 225 mm
Width 140 mm
Depth 226 mm
Net weight 7.5 kg