Push Buttons, Switches, Pilot Lights and Joystick
XB5AS9442 - Emergency Stop - Key - 1NC
- $55.60
Emergency stop switching off, plastic, red mushroom Ø40, Ø22 trigger latching key release, 1NC
Out Of Stock
This product is out of stock, submit your email and we will update once it restock.
range of product | Harmony XB5 |
---|---|
product or component type | Emergency stop push-button Emergency switching off push-button |
device short name | XB5 |
bezel material | Dark grey plastic |
fixing collar material | Plastic |
head type | Standard |
mounting diameter | 22 mm |
sale per indivisible quantity | 1 |
shape of signalling unit head | Round |
type of operator | Trigger action and mechanical latching |
reset | Key release |
operator profile | Red mushroom Ø 40 mm, unmarked |
type of keylock | Ronis 455 |
key withdrawal position | Center |
contact operation | Slow-break |
connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN 60947-1 |
device presentation | Complete product |
height | 43 mm |
---|---|
width | 40 mm |
depth | 100 mm |
terminals description ISO n°1 | (11-12)NC |
net weight | 0.075 kg |
resistance to high-pressure washer | 7000000 Pa at 55 °C, distance: 0.1 m |
contacts usage | Standard contacts |
positive opening | With conforming to EN/IEC 60947-5-1 appendix K |
operating travel | 1.5 mm (NC changing electrical state) 4.3 mm (total travel) |
mechanical durability | 300000 cycles |
tightening torque | 0.8…1.2 N.m conforming to EN 60947-1 |
shape of the screw head | Cross compatible with Philips no 1 screwdriver Cross compatible with Pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver |
contacts material | Silver alloy (Ag/Ni) |
short-circuit protection | 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1 |
[Ith] conventional free air thermal current | 10 A conforming to EN/IEC 60947-5-1 |
[Ui] rated insulation voltage | 600 V (pollution degree 3) conforming to EN 60947-1 |
[Uimp] rated impulse withstand voltage | EN 60947-1 6 kV |
[Ie] rated operational current | 3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1 6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1 |
electrical durability | 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
electrical reliability | Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC 60947-5-4 Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC 60947-5-4 |