Schneider Electric | GV2P22 | Motor Circuit Breaker

Call Us +65 8693 8729
phone 0
phone 0
Product

Contactor and Protection Relay

GV2P22 - Motor Circuit Breaker - 25A

  • $134.82

Motor circuit breaker, TeSys Deca, 3P, 20-25 A, thermal magnetic, screw clamp terminals

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

rangeTeSys
product nameTeSys GV2
product or component type     Circuit breaker
device short nameGV2P
device applicationMotor
trip unit technologyThermal-magnetic
poles description3P
network typeAC
utilisation categoryAC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency50/60 Hz conforming to IEC 60947-4-1
fixing mode35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
operating positionAny position
motor power kW11 kW at 400/415 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity     100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
control typeRotary knob
[In] rated current25 A
thermal protection adjustment range20…25 A
magnetic tripping current327 A
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current25 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage6 kV IEC 60947-2
power dissipation per pole2.5 W
mechanical durability100000 cycles
electrical durability100000 cycles for AC-3 at 440 V
maximum operating rate25 cyc/h
rated dutyContinuous conforming to IEC 60947-4-1
tightening torque1.7 N.m on screw clamp terminals
suitability for isolationYes conforming to IEC 60947-1
phase failure sensitivityYes conforming to IEC 60947-4-1
height89 mm
width45 mm
depth97 mm