Schneider Electric | GVAN11 | Motor Circuit Breaker

Call Us +65 8693 8729
phone 0
phone 0
Product

Industrial Automation

GVAN11 - Side Auxiliary

  • $12.60

TeSys Deca - auxiliary contact block - 1 NO + 1 NC

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range TeSys
TeSys Deca
device short name GVAN
product or component type      Auxiliary contact block
product compatibility GV2ME
GV2RT
GV2L
GV3P
GV3L
GV2LE
GV2P
mounting location Left side
pole contact composition 1 NO + 1 NC
[Ui] rated insulation voltage 600 V conforming to UL 508
690 V conforming to IEC 60947-1
600 V conforming to CSA C22.2 No 14
[Ue] rated operational voltage 48...690 V AC
24...240 V DC
[Ith] conventional free air thermal current      6 A
protection type GB2CB... circuit breaker
GG fuse 10 A
mechanical durability 100000 cycles
minimum switching current 5 mA
minimum switching voltage 17 V
rated operational power in VA 300 VA at 48 V AC-15 - electrical durability: 100000 cycles
414 VA at 690 V AC-15 - electrical durability: 100000 cycles
500 VA at 110…127 V AC-15 - electrical durability: 100000 cycles
500 VA at 500 V AC-15 - electrical durability: 100000 cycles
650 VA at 440 V AC-15 - electrical durability: 100000 cycles
720 VA at 230…240 V AC-15 - electrical durability: 100000 cycles
850 VA at 380…415 V AC-15 - electrical durability: 100000 cycles
rated operational power in W 120 W at 240 V DC-13 - electrical durability: 100000 cycles
140 W at 110 V DC-13 - electrical durability: 100000 cycles
140 W at 24 V DC-13 - electrical durability: 100000 cycles
180 W at 60 V DC-13 - electrical durability: 100000 cycles
240 W at 48 V DC-13 - electrical durability: 100000 cycles
tightening torque 1.4 N.m - on screw clamp terminals
height 89 mm
width 9.3 mm
depth 66 mm
net weight 0.05 kg
colour Dark grey