Schneider Electric | GV3P80 | Motor Circuit Braker

Call Us +65 8693 8729
phone 0
phone 0
Product

Industrial Automation

GV3P80 - Motor Circuit Breaker - 80 A

  • $398.50

Motor circuit breaker, TeSys Deca, 3P, 70-80 A, thermal magnetic, EverLink terminals

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range of product TeSys GV3
range TeSys
TeSys Deca
device short name GV3P
product name TeSys GV3
TeSys Deca
product or component type      Circuit breaker
device application Motor
trip unit technology Thermal-magnetic
poles description 3P
network type AC
utilization category AC-3 conforming to IEC 60947-4-1
network frequency 50/60 Hz
fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
operating position Any position, no direct mounting with contactor, use cable length > 10 cm
Any position, do not use with accessory GV3S
motor power kW 45 kW at 400/415 V AC 50/60 Hz maximum peak current 750 A
45 kW at 500 V AC 50/60 Hz maximum peak current 750 A
55 kW at 690 V AC 50/60 Hz maximum peak current 750 A
breaking capacity 50 kA Icu at 400/415 V AC 50/60 Hz
50 kA Icu at 440 V AC 50/60 Hz
12 kA Icu at 500 V AC 50/60 Hz
6 kA Icu at 690 V AC 50/60 Hz
65 kA Icu at 230/240 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity      100 % at 230/240 V AC 50/60 Hz
60 % at 400/415 V AC 50/60 Hz
60 % at 440 V AC 50/60 Hz
50 % at 500 V AC 50/60 Hz
50 % at 690 V AC 50/60 Hz
control type Rotary knob
[In] rated current 80 A
thermal protection adjustment range 70…80 A
magnetic tripping current 1120 A
[Ue] rated operational voltage 690 V AC 50/60 Hz
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
power dissipation per pole 8 W
mechanical durability 50000 cycles
electrical durability 20000 cycles for AC-3 at 415 V In
maximum operating rate 25 cyc/h
rated duty Continuous conforming to IEC 60947-4-1
tightening torque 5 N.m on EverLink BTR screw connectors for cable 25 mm²
8 N.m on EverLink BTR screw connectors for cable 35 mm²
mechanical robustness Shocks: 30 Gn for 11 ms opened conforming to IEC 60068-2-27
Vibrations: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Shocks: 5 Gn for 11 ms closed conforming to IEC 60068-2-27
phase failure sensitivity Yes conforming to IEC 60947-4-1
height 132 mm
width 55 mm
depth 136 mm
net weight 0.96 kg
color Dark grey
Green (SE GREEN 2)
suitability for isolation Yes conforming to IEC 60947-1