Schneider Electric | GV3P40 | Motor Circuit Breaker

Call Us +65 8693 8729
phone 0
phone 0
Product

Industrial Automation

GV3P40 - Motor Circuit Breaker - 40A

  • $228.48

Motor circuit breaker, TeSys Deca, 3P, 30-40 A, thermal magnetic, EverLink terminals

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range of product TeSys GV3
range TeSys
TeSys Deca
device short name GV3P
product name TeSys GV3
TeSys Deca
product or component type      Circuit breaker
device application Motor
trip unit technology Thermal-magnetic
poles description 3P
network type AC
utilization category AC-3 conforming to IEC 60947-4-1
network frequency 50/60 Hz conforming to IEC 60947-4-1
fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
operating position Any position
motor power kW 18.5 kW at 400/415 V AC 50/60 Hz
22 kW at 500 V AC 50/60 Hz
37 kW at 690 V AC 50/60 Hz
breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity      100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control type Rotary knob
[In] rated current 40 A
thermal protection adjustment range 30…40 A
magnetic tripping current 560 A
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current 40 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
power dissipation per pole 8 W
mechanical durability 50000 cycles
electrical durability 50000 cycles for AC-3 at 415 V In
maximum operating rate 25 cyc/h
rated duty Continuous conforming to IEC 60947-4-1
tightening torque 5 N.m on EverLink BTR screw connectors for cable 25 mm²
8 N.m on EverLink BTR screw connectors for cable 35 mm²
phase failure sensitivity Yes conforming to IEC 60947-4-1
height 132 mm
width 55 mm
depth 136 mm
net weight 0.96 kg
color Dark grey
suitability for isolation Yes conforming to IEC 60947-1