The Schneider Electric Acti9 iDPN Vigi is a Residual Current Breaker with Overcurrent protection (RCBO) designed mainly for residential and small commercial distribution boards. It combines three protections in one device:

  • Earth‑leakage (residual current) protection
  • Overload protection
  • Short‑circuit protection

This means one iDPN Vigi can replace an MCB + RCCB combination on a final circuit.


What the “iDPN Vigi” name means

  • iDPN → Modular single‑phase Acti9 protection device
  • Vigi → Integrated residual current (earth leakage) protection
  • RCBO → Residual current breaker with overcurrent protection

 In practice, the phase is protected, neutral is switched, and earth‑leakage detection is built in.


Key technical characteristics

1. Protection functions

The iDPN Vigi provides:

  • Protection against electric shock(direct & indirect contact)
  • Overload protection(thermal)
  • Short‑circuit protection(magnetic)
  • Isolation function

All in a single 1P+N device.


2. Earth‑leakage protection

Typical ratings depend on the model:

  • Sensitivity: commonly 30 mA(personal protection)
  • Types:
    • Type AC – detects sinusoidal AC leakage
    • Type A – detects AC + pulsating DC (recommended for modern appliances)

Residual current operation is voltage‑independent and instantaneous.


3. Overcurrent & short‑circuit protection

  • Rated current (In): typically 6 A to 40 A
  • Tripping curves: B or C
  • Breaking capacity: 6 kA (6000 A) at 230–240 V AC
  • Limitation class: 3

This makes it suitable for final circuits, not high‑fault industrial incomers.


4. Poles, size & mounting

  • Configuration: 1P + N
  • Width: 36 mm(4 × 9‑mm modules)
  • Mounting: 35 mm DIN rail
  • IP rating: IP20 (IP40 in enclosure)
  • Control: Toggle with ON / OFF / fault trip indication

Standards & compliance

The iDPN Vigi complies with:

  • IEC / EN 61009‑2‑1(RCBO standard)
  • Provides isolation in accordance with IEC / EN 60947‑2

This makes it compliant with modern international wiring standards.


Typical applications

The iDPN Vigi RCBO is commonly used for:

  • Socket‑outlet circuits
  • Lighting circuits
  • Water heaters
  • Dedicated appliance circuits
  • Residential distribution boards
  • Small commercial panels

Each circuit can have individual earth‑leakage protection, so a fault on one circuit doesn’t trip the whole board.


iDPN Vigi vs iC60 + Vigi – quick comparison

Feature iDPN Vigi RCBO iC60 + Vigi
Device type All‑in‑one RCBO Modular MCB + RCD
Breaking capacity 6 kA Up to 50–70 kA (series‑dependent)
Footprint per circuit 36 mm Typically wider
Best use Homes, small commercial Commercial & industrial
Circuit selectivity Per circuit Group or circuit level

In one sentence

The Acti9 iDPN Vigi RCBO is a compact, all‑in‑one solution that protects people and circuits from earth leakage, overload, and short‑circuits—ideal for modern residential and light commercial installations.