Schneider Electric | C40N32D400 | Moulded Case Circuit Breaker

Call Us +65 8693 8729
phone 0
phone 0
Product

Power Distribution

C40N32D400 - MCCB - NSX - Electronic - 400A

  • $781.90

Circuit breaker ComPacT NSX400N, 50kA at 415VAC, MicroLogic 2.3 trip unit 400A, 3 poles 3d

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

IFrame

rangeComPacT new generation
product nameComPacT NSX new generation
range of productComPacT NSX400...630 new generation
device short nameNSX400N
product or component typeCircuit breaker
device applicationDistribution
poles description3P
protected poles description3t
[In] rated current400 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
network typeAC
network frequency50/60 Hz
suitability for isolationYes conforming to EN/IEC 60947-2
utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity     85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508
50 kA at 480 V AC 50/60 Hz conforming to UL 508
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelN 50 kA 415 V AC
trip unit nameMicrologic 2.3
trip unit technologyElectronic
trip unit protection functionsLSoI
control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability15000 cycles
electrical durability3000 cycles at 690 V In
6000 cycles at 690 V In/2
6000 cycles at 440 V In
12000 cycles at 440 V In/2
mounting supportBackplate
upside connectionFront
downside connectionFront
connection pitch45 mm
protection typeL : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
trip unit rating400 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)     Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range160…400 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir
16 s at 6 x Ir
400 s at 1.5 x Ir
thermal memory20 minutes before and after trip
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range4800 A
earth-leakage protectionWithout
Number of slots for electrical auxiliaries6 slot(s)
local signallingFlashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
net weight6.05 kg