Power Distribution

C25F3MA220 - MCCB - NSX - Motor - 220A

  • $569.80

Circuit breaker ComPacT NSX250F, 36kA at 415VAC, MA trip unit 220A, 3 poles 3d

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range ComPacT new generation
product name ComPacT NSX new generation
range of product ComPacT NSX100...250 new generation
device short name NSX250F
product or component type Circuit breaker
device application Motor
poles description 3P
protected poles description 3t
[In] rated current 220 A at 65 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
network type AC
network frequency 50/60 Hz
suitability for isolation Yes conforming to EN/IEC 60947-2
utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity      85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 600 V AC 50/60 Hz conforming to UL 508
Performance level F 36 kA 415 V AC
trip unit name MA
trip unit technology Magnetic
trip unit protection functions I
control type Toggle
Circuit breaker mounting mode Fixed
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability 20000 cycles
electrical durability 5000 cycles at 690 V In
10000 cycles at 690 V In/2
10000 cycles at 440 V In
20000 cycles at 440 V In/2
mounting support Backplate
upside connection Front
downside connection Front
connection pitch 35 mm
protection type I : for short-circuit protection (magnetic)
trip unit rating 220 A at 65 °C
Short-time protection pick-up adjustment type Isd   Adjustable
[Isd] Short-time protection pick-up adjustment range      9...14 x In
earth-leakage protection Without
Number of slots for electrical auxiliaries 5 slot(s)
Width (W) 105 mm
Height (H) 161 mm
Depth (D) 86 mm
net weight 2.4 kg