Schneider Electric | C10F3TM100 | Moulded Case Circuit Breaker

Call Us +65 8693 8729
phone 0
phone 0
Product

Power Distribution

C10F3TM100 - MCCB - NSX - TMD - 100A

  • $282.00

Circuit breaker ComPacT NSX100F, 36kA at 415VAC, TMD trip unit 100A, 3 poles 3d

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

IFrame

rangeComPacT new generation
product nameComPacT NSX new generation
range of productComPacT NSX100...250 new generation
device short nameNSX100F
product or component typeCircuit breaker
device applicationDistribution
poles description3P
protected poles description3t
[In] rated current100 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
network typeAC
network frequency50/60 Hz
suitability for isolationYes conforming to EN/IEC 60947-2
utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity     10 kA at 600 V AC 50/60 Hz conforming to UL 508
25 kA at 480 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelF 36 kA 415 V AC
trip unit nameTM-D
trip unit technologyThermal-magnetic
trip unit protection functionsLI
control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability50000 cycles
electrical durability10000 cycles at 690 V In
20000 cycles at 690 V In/2
30000 cycles at 440 V In
50000 cycles at 440 V In/2
mounting supportBackplate
upside connectionFront
downside connectionFront
connection pitch35 mm
protection typeL : for overload protection (thermal)
I : for short-circuit protection (magnetic)
trip unit rating100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)     Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In
15 s at 6 x Ir
Short-time protection pick-up adjustment type IsdFixed
[Isd] Short-time protection pick-up adjustment range800 A
Short-time protection delay adjustment type tsdFixed
earth-leakage protectionWithout
Number of slots for electrical auxiliaries5 slot(s)
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
net weight2.05 kg