A9F84306

Call Us +65 8693 8729
phone 0
phone 0
Product

Power Distribution

A9F84306

  • $48.30

MCB, iC60H, 3P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

device application

Distribution

 
range

Acti 9

 
product name

Acti 9 iC60

 
product or component type    

Miniature circuit-breaker

 
device short name

IC60H

 
poles description

3P

 
number of protected poles

3

 
[In] rated current

6 A

 
network type

DC
AC

 
trip unit technology

Thermal-magnetic

 
curve code

C

 
breaking capacity

10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2

 
utilisation category

Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2

 
suitability for isolation

Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2

 
standards

IEC 60947-2
EN 60947-2
EN 60898-1
IEC 60898-1

network frequency

50/60 Hz

 
magnetic tripping limit

8 x In +/- 20 %

 
[Ics] rated service breaking capacity

15 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 - 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 - 125...180 V DC
15 kA 100 % conforming to EN 60947-2 - 125...180 V DC

 
limitation class

3 conforming to EN 60898-1
3 conforming to IEC 60898-1

 
[Ui] rated insulation voltage

500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2

 
[Uimp] rated impulse withstand voltage

6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2

 
contact position indicator

Yes

 
control type

Toggle

 
local signalling

Trip indicator

 
mounting mode

Fixed

 
mounting support

DIN rail

 
comb busbar and distribution block compatibility    

Top or bottom: YES

 
9 mm pitches

6

 
height

85 mm

 
width

54 mm

 
depth

78.5 mm

 
net weight

0.375 kg

 
colour

White

 
mechanical durability

20000 cycles

 
electrical durability

10000 cycles

 
connections - terminals

Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible

 
wire stripping length

14 mm for top or bottom connection

 
tightening torque

2 N.m top or bottom

 
earth-leakage protection

Separate block