LUB38 -Power Base - 38A

  • $309.20

Power base, TeSys Ultra, 3P, 38A/690V

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

RangeTeSys
Product nameTeSys Ultra
Device short nameLUB
Product or component typeNon reversing power base
Device applicationMotor control
Motor protection
Poles description3P
Suitability for isolationYes
[Ue] rated operational voltage690 V AC for power circuit
Network frequency40...60 Hz
[Ith] conventional free air thermal current     38 A
[Ie] rated operational current35 A at <= 440 V
28 A at 500 V
24 A at 690 V
utilisation categoryAC-43
AC-41
[Ics] rated service breaking capacity25 kA at 230 V
25 kA at 440 V
10 kA at 500 V
4 kA at 690 V
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typeType linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1
type mirror contact (1 NC) conforming to IEC 60947-1
[Uc] control circuit voltage24 V AC 50/60 Hz
24 V DC
48...72 V AC 50/60 Hz
48...72 V DC
110...240 V AC 50/60 Hz
110...220 V DC
Typical current consumption200 mA at 24 V DC I maximum while closing with LUCM
220 mA at 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
220 mA at 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
25 mA at 110...220 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
25 mA at 110...240 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
280 mA at 110...220 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 110...240 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
45 mA at 48...72 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
45 mA at 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
75 mA at 24 V DC I rms sealed with LUCM
80 mA at 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
90 mA at 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
Heat dissipation3 W for control circuit with LUCA, LUCB, LUCC, LUCD
1.8 W for control circuit with LUCM
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Operating time35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM for control circuit
50 ms at >= 72 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
65 ms closing with LUCM for control circuit
Mechanical durability15 Mcycles
Maximum operating rate3600 cyc/h
product certificationsCE
UL
CSA
CCC
EAC
StandardsEN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
[Ui] rated insulation voltage690 V conforming to IEC 60947-6-2 (pollution degree 3)
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage     6 kV conforming to IEC 60947-6-2
Safe separation of circuit400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N
Fixing modeClipped (DIN rail)
Screw-fixed (plate)
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 0.34…1.5 mm² flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² rigid
Control circuit: screw clamp terminals 2 cable(s) 0.34…1.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² rigid
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm² rigid
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² rigid
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² flexible without cable end
Tightening torqueControl circuit: 0.8…1.2 N.m flat screwdriver 5 mm
Control circuit: 0.8…1.2 N.m Philips no 1 screwdriver 5 mm
Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm
Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm
Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm
Width45 mm
height154 mm
Depth126 mm
Net weight0.9 kg
Compatibility codeLUB