Schneider Electric | 56272 | Earth Leakage Relay

Call Us +65 8693 8729
phone 0
phone 0
Product

Power Distribution

56272 - Earth Leakage Relay - 130VAC

  • $226.10

residual current protection relay, VigiPacT RH99P, 30 mA to 30 A, 110/130 VAC 50/60 Hz, front panel mounting

Out Of Stock

This product is out of stock, submit your email and we will update once it restock.

range VigiPacT
device short name RH99P
product or component type Residual current protection relay
relay application Protection relay
mounting support Front panel
earth-leakage protection class Type A
type of setting Selector
residual earth-leakage sensitity adjustment type      Adjustable 9 settings
Earth-leakage sensitivity 0.03…30 A
Earth-leakage time delay Instantaneous for 0.03 A
Adjustable 9 settings 0…4.5 s for 0.03…30 A
Current sensors compatibility TOA earth leakage current sensor
A earth leakage current sensor
L earth leakage current sensor
[Ithe] conventional enclosed thermal current 8 A
minimum load 10 mA at 12 V
[Us] rated supply voltage 110...130 V AC 50/60 Hz 55...110 %
power consumption in VA 4 VA
Monitored distribution system 1000 V - AC at 50/60 Hz (maximum)
1000 V - AC at 400 Hz (maximum)
earthing system TN-S
IT
TT
[Uimp] rated impulse withstand voltage 8 kV
reset Manual reset
test function Remote test
Local
monitoring Electronics (continuous)
Power supply (continuous)
Relay/sensor link (continuous)
type of measurement Earth fault current internal measurement, range: 80...100 %
tamperproof of settings Protected by sealable cover
connections - terminals Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Fault: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Fault: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
Fault: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Relay test and fault reset: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Relay test and fault reset: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
Relay test and fault reset: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Sensor: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Sensor: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
Sensor: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Voltage presence: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Voltage presence: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
Voltage presence: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
wire stripping length Auxiliary power supply: 7 mm
Fault: 7 mm
Relay test and fault reset: 7 mm
Sensor: 7 mm
Voltage presence: 7 mm
tightening torque Auxiliary power supply: 0.6 N.m
Fault: 0.6 N.m
Relay test and fault reset: 0.6 N.m
Sensor: 0.6 N.m
Voltage presence: 0.6 N.m
width 72 mm
height 72 mm
depth 78 mm
cut-out dimensions 68 x 68 mm
net weight 0.3 kg
IP degree of protection IP40 on front face: conforming to EN/IEC 60529
IP30 on side parts: conforming to EN/IEC 60529
IP20 on connection terminals: conforming to EN/IEC 60529
IK degree of protection      IK07 conforming to EN 50102
mechanical robustness Fire resistance conforming to IEC 60695-2-1
IK protection 2 joules: IK07 conforming to EN 50102
Vibrations 13.2...100 Hz: 0.7 g
Vibrations 2...13.2 Hz: +/- 1 mm